Serial Communication Programmer Reference Guide
18 810400 Reference Guide Powermax65/85/105 SYNC
Request: Write operating settings and put the plasma power supply into remote control mode
0x3080 Operating mode setting N/A 10 (Write Multiple Registers) 0x2093
0x3081 Output current (A) setting Amperes 10 (Write Multiple Registers) 0x2094
0x3082 Gas pressure setting psi 10 (Write Multiple Registers) 0x2096
Request: Do a quick restart of the plasma power supply or clear fault code 0-50-0
0x308E Quick restart command
(Write a value of 0x0404 to this address.)
N/A 10 (Write Multiple Registers) N/A
0x308F Quick restart approval
(Write a value of 0x0618 to this address.)
N/A 10 (Write Multiple Registers) N/A
Request: Read the Start and Motion signal status of the plasma power supply
0x3100
(coil)
Start switch signal status
(ON = 1, OFF = 0)
N/A 01 (Read Coil) 0x0810
0x3101
(coil)
Motion switch signal status
(ON = 1, OFF = 0)
N/A 01 (Read Coil) 0x0811
Request: Start and stop a gas test
0x3180
(coil)
Gas test status
(Write a value of 0xFF00 to this coil to start a
gas test.)
(Write a value of 0x0000 to this coil to stop a
gas test.)
N/A 05 (Write Single Coil) 0x0832
SYNC
Address
Description Unit
Recommended Modbus
Function (hex)
Old
Address