80010901-1406ffff Numeric sensor [NumericSensorElementName] going high (upper critical) has asserted.
Explanation: IMM has detected that the temperature of a system board voltage regulator has risen above the upper
critical threshold.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0494
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80010901-1407ffff Numeric sensor [NumericSensorElementName] going high (upper critical) has asserted.
Explanation: IMM has detected that the temperature of a microprocessor and memory expansion tray voltage
regulator has risen above the upper critical threshold.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0494
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80010901-1408ffff Numeric sensor [NumericSensorElementName] going high (upper critical) has asserted.
Explanation: IMM has detected that the temperature of a microprocessor and memory expansion tray voltage
regulator has risen above the upper critical threshold.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0494
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80010901-1406ffff 80010901-1408ffff
406
System x3750 M4 Types 8722 and 8733: Installation and Service Guide