122 IBM System x3850 X6 and x3950 X6 Planning and Implementation Guide
4.6 Cooling advice
It is important to maintain sufficient temperature and humidity control in the data center
environment to prevent thermal failures. Use the following information to help plan for proper
cooling of the X6 servers and rack components:
򐂰 The airflow is from the front to the back. Make sure that the airflow to the server is
unobstructed at all times.
򐂰 Install the server and devices only in a rack that has perforated front and rear doors with
sufficient openings to allow for proper airflow.
򐂰 Always install rack filler panels in empty bays to help ensure proper air circulation.
򐂰 Install side covers on single racks to help prevent air recirculation.
򐂰 Multiple racks placed side by side must have side covers or be joined together as a suite
to prevent air recirculation between the racks.
򐂰 Install a skirt or the recirculation prevention bracket on the front of the rack to prevent air
circulation below the rack.
If you plan to install the optional IBM Rear Door Heat eXchanger V2 on the IBM 42U
1100 mm Enterprise V2 Dynamic Rack, consider the following requirements:
򐂰 Chilled, conditioned water must be provided that meets the heat exchanger specifications.
򐂰 A water supply system must be installed that is suitable for your data center.
򐂰 A redundant secondary cooling loop water supply, or enough room air conditioning to
handle the heat load must be provided if the function of one or more of the heat
exchangers is compromised. For example, if the rear door is opened for rack maintenance
or the conditioned water supply to the door is stopped, the rack heat load is sent out into
the room and must be handled by room air conditioning until the conditioned water supply
is restored.
򐂰 Protective coverings should be installed to avoid tripping hazards on non-raised floors as
part of the water hose management.
򐂰 The rack must have front and rear doors with at least 60% open area for airflow.
򐂰 The rack must have front to back airflow.
It is important to prevent hot air recirculation from the back of the rack to the front. An air
sealing plane should be established at the front of the rack at the location of the vertical EIA
flanges. The following should be considered:
򐂰 All U spaces must be occupied at the front EIA air sealing plane by either a device or a U
space filler.

Table of Contents

Other manuals for IBM X3850 X6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM X3850 X6 and is the answer not in the manual?

IBM X3850 X6 Specifications

General IconGeneral
ChipsetIntel C602J
Network ControllerIntegrated quad-port Gigabit Ethernet
ProcessorUp to four Intel Xeon E7-4800 v2 series processors or Intel Xeon E7-8800 v2 series processors
MemoryUp to 6 TB of DDR3 ECC Registered DIMMs (RDIMMs) or Load-Reduced DIMMs (LRDIMMs)
Form Factor4U rack server
StorageUp to 24x 2.5" hot-swap SAS/SATA HDDs or SSDs
Expansion SlotsUp to 11 PCIe 3.0 slots
Power SupplyUp to four 1400W or 900W hot-swap power supplies
Memory TypeDDR3 RDIMM/LRDIMM
Storage ControllerServeRAID M5210 SAS/SATA controller
RAID SupportRAID 0, 1, 5, 6, 10, 50, 60
Operating System SupportWindows Server, Red Hat Enterprise Linux, SUSE Linux Enterprise Server, VMware

Related product manuals