WindO/I-NV4 Users Manual 27-7
2 Pass-Through Function Settings Procedure
27
Pass-Through Function
7 Press Pass-Through Setting (HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F) or press Pass Through (HG2G-5T, HG1G/
1P).
8
Select the Enable PassThrough check box and press Save (HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F) or SAVE
(HG2G-5T, HG1G/1P).
When the setting is saved, "The value was updated." is displayed.
This concludes the configuration to enable the Pass-through function.
Trans. Wait Pass-Through
Retry Cycles Time Out
Parameter3 Parameter4
Parameter2Parameter1
Ext.
Device 1
Ext.
Device
Initial
Setting
Main
Menu
Save Cancel
Enable PassThrough
The value was updated.
Ext.
Device 1
Ext.
Device
Initial
Setting
Main
Menu