WindO/I-NV4 Users Manual 10-37
2 Character Input
10
Data Displays
Display Character with “*”
*1
Select this check box to display the entered characters as * (asterisks).
If this check box is selected, nothing is displayed until a value is entered from the key buttons or keypad when the
Character Input is in entry mode. If
ENT
is pressed with nothing displayed, 0 is written to the destination device address.
Change Font with Device Address
*1
Select this check box to change the font used to display the text with a value of device address.
The keypad (popup screen) can also be changed when Standard(Half-Width Character), Standard(Hiragana)
or Popup is selected for Type under Keypad on the General tab.
Change Display Colors
Select this check box to switch the text and plate colors.
*1 Advanced mode only
Trigger Device Address: Specifies the word device (2 words) to use as the condition to change the font.
Click to display the Tag Editor. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-68.
Example: With Trigger Device Address set to D100, to enter Central European text from
popup screen 100 using a Character Input for entering European text from the
standard keypad (popup screen 3003)
Write 6 to D100 and 100 to D101.
Font number Popup screen No.
1st word 3rd word2nd word
Font number
1: Japanese
2: European
6: Central European
7: Baltic
8: Cyrillic
Popup screen No. 1 to 3015
Trigger Device Address: Specifies the bit device or the bit number of the word device to use as the trigger to switch
the text and plate colors.
Click to display the Tag Editor. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-68.
When the value of device address is 0, the color specified in Text Color or in Plate Color
on the View tab will be displayed.
When the value of device address is 1, the color displayed and specified in Text Color or
Plate Color
under the Change Display Colors.
Text Color: Selects the color (color: 256 colors, monochrome: 16 shades) of the text when switching.
Click this button to display the Color Palette. Select a color from the Color Palette.
Plate Color: Selects the plate color (color: 256 colors, monochrome: 16 shades) when switching.
Click this button to display the Color Palette. Select a color from the Color Palette.
This option can only be configured when
Standard
is selected for
Image Type
on the
View
tab.
MICRO/I
0
1
Trigger Device Address
Trigger Device Address
External device
HGSERIES
HGSERIES
Text Color
Plate Color on the View tab
Text Color under Change Display Colors
Plate Color under Change Display Colors

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC MICRO/I HG1G-4VT22TF Series and is the answer not in the manual?

IDEC MICRO/I HG1G-4VT22TF Series Specifications

General IconGeneral
BrandIDEC
ModelMICRO/I HG1G-4VT22TF Series
CategoryControl Panel
LanguageEnglish

Related product manuals