9: F
UNCTIONAL
M
ODULES
9-8 FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
(8) Status
The status of the analog input data (7) is stored in data registers.
Status Description
0 Operating normally
1 Converting data
2 Initializing
3 Parameter setting error
4 Hardware fault (external power supply error)
5 Wiring fault (out of maximum range)
*1
6 Wiring fault (out of minimum range)
*1
7 Reserved
8 When the analog input value is greater than 20 mA and less than the upper limit value
*2
9 When the analog input value is greater than the lower limit value and less than 4 mA
*3
10 to 65,535 Reserved
*1 When the analog input value is the upper limit value in the below table or higher, the out of maximum range error occurs. When the analog
input value is the lower limit value in the below table or lower, the out of minimum range error occurs.
Signal Type Lower Limit Value Upper Limit Value
0 to 10 V -0.2 V 10.2 V
-10 to +10 V -10.4 V 10.4 V
0 to 20 mA -0.4 mA 20.4 mA
4 to 20 mA 3.68 mA 20.32 mA
Type K thermocouple -200.0°C 1,300.0°C
Type J thermocouple -200.0°C 1,000.0°C
Type R thermocouple 0.0°C 1,760.0°C
Type S thermocouple 0.0°C 1,760.0°C
Type B thermocouple 0.0°C 1,820.0°C
Type E thermocouple -200.0°C 800.0°C
Type T thermocouple -200.0°C 400.0°C
Type N thermocouple -200.0°C 1,300.0°C
Type C thermocouple 0.0°C 2,315.0°C
Pt100 -200.0°C 850.0°C
Pt1000 -200.0°C 600.0°C
NI100 -60.0°C 180.0°C
NI1000 -60.0°C 180.0°C
NTC thermistor 100 Ω 200 kΩ
PTC thermistor -90.0°C/100 Ω 150.0°C/10 kΩ
PTC thermistor (threshold) 100 Ω 10 kΩ
Resistance measurement 100 Ω 32 kΩ
Expansion 0 to 20 mA -0.4 mA 23.54 mA
Expansion 4 to 20 mA 1.20 mA 23.17 mA
*2 Expansion 0 to 20 mA or expansion 4 to 20 mA only