2: P
RODUCT
S
PECIFICATIONS
2-8 FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
S
M
ANUAL
FC9Y-B1722
Power Supply Specifications
AC Power Type
Type No. FC6A-C16R1AE, FC6A-C24R1AE, FC6A-C40R1AE, FC6A-C40R1AEJ
Rated Operating Voltage 100 to 240V AC
Voltage Fluctuation Range 85 to 264V AC
Rated Power Frequency 50/60 Hz (47 to 63 Hz)
Maximum Power Consumption Standalone When Maximum Load is Connected
FC6A-C16R1AE 33 VA 54 VA
FC6A-C24R1AE 35 VA 61 VA
FC6A-C40R1AE 41 VA 74 VA
FC6A-C40R1AEJ 37 VA 74 VA
Allowable Momentary Power
Interruption
10 ms or longer (when rated power supply voltage)
Withstand Voltage
Between power and PE terminals: 1,500V AC, 1 minute
Between input and PE terminals: 1,500V AC, 1 minute
Between relay output and PE terminals: 2,300V AC, 1 minute
Between power and input terminals: 1,500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
Insulation Resistance
Between power and PE terminals: 100 M or higher (500V DC insulation resistance tester)
Between input and PE terminals: 100 M or higher (500V DC insulation resistance tester)
Between relay output and PE terminals: 100 M or higher (500V DC insulation resistance tester)
Between power and input terminals: 100 M or higher (500V DC insulation resistance tester)
Between power and relay output terminals: 100 M or higher (500V DC insulation resistance tester)
Between input and relay output terminals: 100 M or higher (500V DC insulation resistance tester)
Inrush Current 40 A maximum
Isolation Between power terminal and internal circuit: Transformer isolated
Ground D-type ground (Class 3 ground)
Grounding Wire See "Recommended Ferrule List" on page 3-35
Power Supply Wire See "Recommended Ferrule List" on page 3-35
Effect of Improper Power Supply
Connection
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
Weight
FC6A-C16R1AE 370 g
FC6A-C24R1AE 420 g
FC6A-C40R1AE 560 g
FC6A-C40R1AEJ 560 g