FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722 2-11
2: P
RODUCT
S
PECIFICATIONS
■ 12V DC Power Type
Type No.
FC6A-C40R1DE, FC6A-C40K1DE, FC6A-C40P1DE, FC6A-C40R1DEJ, FC6A-C40K1DEJ,
FC6A-C40P1DEJ
Rated Power Voltage 12V DC
Voltage Fluctuation Range 10.2 to 18V DC (including ripple)
Maximum Power Consumption Standalone When Maximum Load is Connected
FC6A-C40R1DE 4.14 W (12V DC) 23.28 W (12V DC)
FC6A-C40K1DE 3.12 W (12V DC) 23.28 W (12V DC)
FC6A-C40P1DE 3.12 W (12V DC) 23.28 W (12V DC)
FC6A-C40R1DEJ 4.08 W (12V DC) 23.28 W (12V DC)
FC6A-C40K1DEJ 3.84 W (12V DC) 23.28 W (12V DC)
FC6A-C40P1DEJ 3.84 W (12V DC) 23.28 W (12V DC)
Allowable Momentary Power
Interruption
10 ms or longer (when rated power supply voltage)
Withstand Voltage
Between power and FE terminals: 500V AC, 1 minute
Between input and FE terminals: 500V AC, 1 minute
Between transistor output and FE terminals: 500V AC, 1 minute
Between relay output and FE terminals: 2,300V AC, 1 minute
Between power and input terminals: 500V AC, 1 minute
Between power and transistor output terminals: 500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and transistor output terminals: 500V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
Insulation Resistance
Between power and FE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and FE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between transistor output and FE terminals: 100 MΩ or higher (500V DC insulation resistance
tester)
Between relay output and PE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and input terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and transistor output terminals: 100 MΩ or higher (500V DC insulation resistance
tester)
Between power and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and transistor output terminals: 100 MΩ or higher (500V DC insulation resistance
tester)
Between input and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Inrush Current 35 A maximum
Isolation Between power terminal and internal circuit: Transformer isolated
Ground D-type ground (Class 3 ground)
Grounding Wire See "Recommended Ferrule List" on page 3-35
Power Supply Wire See "Recommended Ferrule List" on page 3-35
Effect of Improper Power Supply
Connection
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
Weight
FC6A-C40R1DE 560 g
FC6A-C40K1DE 530 g
FC6A-C40P1DE 530 g
FC6A-C40R1DEJ 560 g
FC6A-C40K1DEJ 530 g
FC6A-C40P1DEJ 530 g