EasyManua.ls Logo

iDect FC6A series - Page 39

iDect FC6A series
474 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
S
M
ANUAL
FC9Y-B1722 2-11
2: P
RODUCT
S
PECIFICATIONS
12V DC Power Type
Type No.
FC6A-C40R1DE, FC6A-C40K1DE, FC6A-C40P1DE, FC6A-C40R1DEJ, FC6A-C40K1DEJ,
FC6A-C40P1DEJ
Rated Power Voltage 12V DC
Voltage Fluctuation Range 10.2 to 18V DC (including ripple)
Maximum Power Consumption Standalone When Maximum Load is Connected
FC6A-C40R1DE 4.14 W (12V DC) 23.28 W (12V DC)
FC6A-C40K1DE 3.12 W (12V DC) 23.28 W (12V DC)
FC6A-C40P1DE 3.12 W (12V DC) 23.28 W (12V DC)
FC6A-C40R1DEJ 4.08 W (12V DC) 23.28 W (12V DC)
FC6A-C40K1DEJ 3.84 W (12V DC) 23.28 W (12V DC)
FC6A-C40P1DEJ 3.84 W (12V DC) 23.28 W (12V DC)
Allowable Momentary Power
Interruption
10 ms or longer (when rated power supply voltage)
Withstand Voltage
Between power and FE terminals: 500V AC, 1 minute
Between input and FE terminals: 500V AC, 1 minute
Between transistor output and FE terminals: 500V AC, 1 minute
Between relay output and FE terminals: 2,300V AC, 1 minute
Between power and input terminals: 500V AC, 1 minute
Between power and transistor output terminals: 500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and transistor output terminals: 500V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
Insulation Resistance
Between power and FE terminals: 100 M or higher (500V DC insulation resistance tester)
Between input and FE terminals: 100 M or higher (500V DC insulation resistance tester)
Between transistor output and FE terminals: 100 M or higher (500V DC insulation resistance
tester)
Between relay output and PE terminals: 100 M or higher (500V DC insulation resistance tester)
Between power and input terminals: 100 M or higher (500V DC insulation resistance tester)
Between power and transistor output terminals: 100 M or higher (500V DC insulation resistance
tester)
Between power and relay output terminals: 100 M or higher (500V DC insulation resistance tester)
Between input and transistor output terminals: 100 M or higher (500V DC insulation resistance
tester)
Between input and relay output terminals: 100 M or higher (500V DC insulation resistance tester)
Inrush Current 35 A maximum
Isolation Between power terminal and internal circuit: Transformer isolated
Ground D-type ground (Class 3 ground)
Grounding Wire See "Recommended Ferrule List" on page 3-35
Power Supply Wire See "Recommended Ferrule List" on page 3-35
Effect of Improper Power Supply
Connection
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
Weight
FC6A-C40R1DE 560 g
FC6A-C40K1DE 530 g
FC6A-C40P1DE 530 g
FC6A-C40R1DEJ 560 g
FC6A-C40K1DEJ 530 g
FC6A-C40P1DEJ 530 g

Table of Contents