2: P
RODUCT
S
PECIFICATIONS
2-12 FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
Function Specifications
■ CPU Module Performance
*1 1 step is equivalent to 8 bytes.
*2 There are limitations on the maximum number of outputs that can be simultaneously turned on.
For details, see "Connection Restrictions for Expansion Modules and Option Modules" on page 3-30.
Backup Function
Clock Function
Type No.
FC6A-C16R1AE
FC6A-C16R1CE
FC6A-C16K1CE
FC6A-C16P1CE
FC6A-C24R1AE
FC6A-C24R1CE
FC6A-C24K1CE
FC6A-C24P1CE
FC6A-C40R1AE
FC6A-C40R1CE
FC6A-C40K1CE
FC6A-C40P1CE
FC6A-C40R1DE
FC6A-C40K1DE
FC6A-C40P1DE
FC6A-C40R1AEJ
FC6A-C40R1CEJ
FC6A-C40K1CEJ
FC6A-C40P1CEJ
FC6A-C40R1DEJ
FC6A-C40K1DEJ
FC6A-C40P1DEJ
Program
Capacity
*1
Program Data
72,000 bytes
(9,000 steps)
* Writable during run-time
384,000 bytes
(48,000 steps)
* Not writable during run-time
640,000 bytes
(80,000 steps)
* Not writable
during run-time
Comment Data 256,000 bytes 256,000 bytes
I/O Expansion
4777
Expansion Interface 8888
I/O Points
Basic
Input 9142424
Output 7101616
Basic Expansion
*2
128 224 224 224
Expansion Interface 256 256 256 256
User Program Storage
Serial flash ROM (write durability: 100,000 times)
CPU internal flash ROM (write durability: 1,000 times)
Control System
Stored program system
Instructions
Basic Instructions 42 types
Advanced
Instructions
124 types
Processing Speed
Basic Instruction 0.042 ms/1,000 steps
END Processing 1 ms
Internal Relay 12,400
Shift Register 256
Data Register 54,000
Counter (adding, reversible) 512
Timer (1 ms, 10 ms, 100 ms, 1 s) 1,024
Backup Data RAM (internal relays, shift registers, counters, data registers), clock
Backup Battery Lithium ion primary cell (replaceable, BR2032)
Backup Duration Guaranteed 1 year, replacement recommended every 4 years at 25°C
Replaceability Yes (within 1 minute after power off)
Accuracy ±30 seconds/month at 25°C
Correction Function
Not available (can be corrected at the factory)