2: P
RODUCT
S
PECIFICATIONS
2-70 FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
â–  Analog Output Specifications
*1 The arbitrary setting is a function that uses the digital resolution data by scaling it to arbitrary data (that arbitrarily sets the lower limit value and
the upper limit value). The range setting (-32,768 to 32,767) is specified with data registers.
Output Internal Circuit
Output Type and Output Range
Voltage Current
0 to 10 V
-10 to 10 V
4 to 20 mA
0 to 20 mA
Load
Impedance 1 kΩ or higher 300 Ω or lower
Load Type Resistive load
DA
Conversion
DA Conversion Time 1 ms
Output Update Interval 1 ms
Total Output System Transfer Time DA conversion time + Output Update Interval + 1 scan time
Output Error
Maximum Error
at 25°C
FC6A-L03CN1 ±0.1% of full scale
FC6A-L06A1
±0.2% of full scale
FC6A-K4A1
Temperature
Coefficient
FC6A-L03CN1 0.006%/°C
FC6A-L06A1
0.01%/°C
FC6A-K4A1
Output Ripple 1 LSB or lower
Overshoot 0%
Data
Digital Resolution 4,096 steps (12 bits)
Input Value per Step
2.44 mV (0 to 10 V)
4.88 mV (-10 to +10 V)
4.88 μA (0 to 20 mA)
3.91 μA (4 to 20 mA)
Application Can be arbitrarily set for each CH in a range between -32,768 to 32,767
*1
Monotonicity Yes
Current Loop Open Not detectable
Noise
Resistance*3
Maximum Temporary Deviation
during Electrical Noise Tests
±4% or less of full scale
Recommended Cable for Noise
Immunity
Current/voltage: Pair shielded cable
Other: Pair cable
Crosstalk 1 LSB
Isolation
Between Output and Power Circuit Transformer isolated
Between Output and Internal Circuit Photocoupler isolated
Effect of Improper Output Connection No damage
Selection of Analog Output Signal Type Using programming software
Calibration or Verification to Maintain Rated Accuracy Not possible
Analog Signal
Switching Signal