SmartPLC SafeLine AC4S with fieldbus interfaces
219
>
Parameter data
43068
Parameter
Data type
Description
Possible values
ASi_SlaveAdr
INT
Address of the AS-i slave
1
...
31
Slave address 1
...
slave address 31
ASi_Master
INT
AS-i master to which the AS-i
slave is connected
1
AS-i Master 1
2
AS-i Master 2
DisableLogging
BOOL
Transmission of the event
messages to OSC of the device
FALSE
Following states of the state diagram
are transmitted to the OSC: *
S_ON
S_OFF
S_Test
S_Error
S_Init (HW-Error)
TRUE
Following states of the state diagram
are transmitted to the OSC:
S_Test
S_Error
S_Init (HW-Error)
EnableStartupTest
BOOL
Control execution of the start-up
test
FALSE
No start-up test *
TRUE
Start-up test is executed; slave waiting
for start-up sequence OFF ON
SynchTime
WORD
Synchronisation time
0
250
...
500
...
60000
Infinite
250 milliseconds
...
500 milliseconds *
...
60000 milliseconds
* ...
Default value
>
Process data
43123
Parameter
Data type
Description
Possible values
S_IN_dependent
SAFEBOOL
Safe process signal
FALSE
Safe OFF
TRUE
Safe ON