EasyManua.ls Logo

IFM Electronic AC402S - Page 223

IFM Electronic AC402S
272 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SmartPLC SafeLine AC4S with fieldbus interfaces
223
>
Parameter data
43065
Parameter
Data type
Description
Possible values
ASi_SlaveAdr
INT
Address of the AS-i slave
1
...
31
Slave address 1
...
slave address 31
ASi_Master
INT
AS-i master to which the AS-i
slave is connected
1
AS-i Master 1
2
AS-i Master 2
DisableLogging
BOOL
Transmission of the event
messages to OSC of the device
FALSE
Following states of the state diagram
are transmitted to the OSC: *
S_ON
S_OFF
S_Test
S_Error
S_Init (HW-Error)
TRUE
Following states of the state diagram
are transmitted to the OSC:
S_Test
S_Error
S_Init (HW-Error)
EnableStartupTest
BOOL
Control execution of the start-up
test
FALSE
No start-up test *
TRUE
Start-up test is executed; slave waiting
for start-up sequence OFF ON
SynchTime
WORD
Synchronisation time
0
250
...
500
...
60000
Infinite
250 milliseconds
...
500 milliseconds *
...
60000 milliseconds
StabilisingTime
WORD
Max. bounce time
250
...
10000
250 milliseconds *
...
10000 milliseconds
* ...
Default value
Process data
43126
Parameter
Data type
Description
Possible values
S_IN_dep_filter_testreq
SAFEBOOL
Safe process signal
FALSE
Safety function OFF
TRUE
Safety function ON
>

Table of Contents

IFM Electronic AC402S - Page 223