EasyManua.ls Logo

IFM Electronic AC402S - Page 95

IFM Electronic AC402S
272 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SmartPLC SafeLine AC4S with fieldbus interfaces
95
>
Step 1: Calculate typical response times
43023
Calculate typical response times of the safety functions of the device:
Without safe cross communication
AS-i output
Local output
FSoE slave output
AS-i input
30 ms +
2*T(SafetyTask) +
15 ms
30 ms +
2*T(SafetyTask) +
8 ms
30 ms +
2*T(SafetyTask) +
4*T(MainTask) +
4*T(MapTask) + 32 ms
Local input
16 ms +
2*T(SafetyTask) +
15 ms
16 ms +
2*T(SafetyTask) +
8 ms
16 ms +
2*T(SafetyTask) +
4*T(MainTask) +
4*T(MapTask) + 32 ms
FSoE Slave
Eingang
32 ms +
4*T(MainTask) +
4*T(MapTask) +
2*T(SafetyTask) +
15 ms
32 ms +
4*T(MainTask) +
4*T(MapTask) +
2*T(SafetyTask) +
8 ms
32 ms +
4*T(MainTask) +
4*T(MapTask) +
2*T(SafetyTask) +
4*T(MainTask) +
4*T(MapTask) + 32 ms
With safe cross communication (Safety NetVars)
To device 2
From device 1
AS-i output
Local output
FSoE slave output
AS-i input
30 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
15 ms
30 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
8 ms
30 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms
Lokaler
Eingang
16 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
15 ms
16 ms
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
8 ms
16 ms
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms
FSoE Slave
Eingang
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
15 ms
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
8 ms
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms
The formula in the table determine only the typical response time of the device. For the
calculation of the typical process response time the delay times of the safety AS-i
sensors/actuators and the respective input/output devices have to be added additionally
(T(sensor) + T(input) and T(output) + T(aktuator)).