SmartPLC SafeLine AC4S with fieldbus interfaces
97
>
Step 3: Define watchdog times
43004
Safe cross communication and safe fieldbus communication are monitored by means of watchdogs.
Sufficiently long watchdog times have to be selected.
Determine the watchdog times on the basis of the maximum response times of the safety function
measured ins step 2. ifm recommends the following formulas:
safe cross communication: T(WD_SafetyNetVars) = 2*T(tMaxRespTimeMS)
safe fieldbus communication: T(WD_FSoE) = 2*T(tMaxRespTimeMS)
Set watchdog times (Set variable components of the response time ( S. 99)).