EasyManua.ls Logo

Inficon IC6

Inficon IC6
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - 20
IPN 074-505-P1E
IC6 Operating Manual
9.5 Logic Statement Example
The logic statement capability of the IC6 allows for automation of a thin film
process. For example, it is possible to start a process without manually pressing
START. One way to accomplish this is:
IF: PROCESS END ANY AND LAYER END ANY
THEN: START
The STOP
can be added to assure that the process does not start again if it was
stopped.
To enter this statement follow this procedure:
1 On the MAIN MENU screen, make sure the state is READY. If it is not, press
STOP, then press RESET.
2 Move the cursor to Logic, then press the MENU key.
3 Using the down arrow, move to one of the Logic x-y pages.
4 From the Logic x -y page, press the right arrow key to move to the statements.
5 Place the cursor on any blank logic statement, using the up and down cursor
keys.
6 Press F1 EDIT.
7 Press F1 EVENT/ACTION.
8 Cursor to LAYER END. Press F3 INSERT. In the upper left of the screen,
LAYER END ### will appear after IF.
9 Cursor to PROCESS END. Press F3 INSERT. PROCESS END ### ccc LAYER
END ### will appear after IF.
10 Press F1 IF/THEN.
11 Cursor down to THEN. Press F1 EVENT/ACTION.
12 Cursor down to START. Press F3 INSERT. Press F1 IF/THEN.
13 Cursor to PROCESS END. Press F1 EVENT/ACTION. Press F4 NEGATE. A
bar will appear above PROCESS END.
14 Press F1 IF/THEN.
15 Cursor to ###. Press 0, Enter. ### will be replaced by ANY.
16 The cursor should now be on ccc. Press TOGL once to change the ccc to AND.
Press Enter.
17 Cursor to ###. Press 0, Enter. The ### will be replaced by ANY.
18 Press F4 SAVE & EXIT to return to the Logic page. At this point the Logic
Statement is entered into memory.