Multitron - Operating Manual
Technical Data and Specifications
Page 146 of 158 20 August 2020
Various
Description Value Unit
Cooling power
2
900
W
Additional mass
3
45
kg
Additional height
290
mm
2
) Cooling power at coolant temperature of 20 °C (room temperature of 20 °C)
3
) Mass including cooling register and cover
Lowest reachable temperature
Description Value Unit
Single unit
18
°C b. AT
4
Two units stacked
17
°C b. AT
Three units stacked
15
°C b. AT
4
) Below ambient temperature
Cooling unit 2 x 900 W
Electrical data
Description Type 230 V Type 115 V Unit
Value
Max. power consumption
1
1080 1080 W
Max. current consumption 8.4 16.8 A
Fuses (5 x 20 mm, slow-blown) 10 - A
Thermal protection switch - 15 A
1
) Power consumption of the compressor
Various
Description Value Unit
Cooling power
2
1800
W
Additional mass
3
80
kg
Additional height
290
mm
2
) Cooling power at coolant temperature of 20 °C (room temperature of 20 °C)
3
) Mass including cooling register and cover