EasyManua.ls Logo

Infors HT Multitron - Temperature Parameter (Heating and Ventilation); Specifications of the Options; Internal Cooling

Infors HT Multitron
161 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multitron - Operating Manual
Technical Data and Specifications
20 August 2020 Page 145 of 158
Maximum rotation speeds with Sticky Stuff adhesive matting
For a detailed description of the maximum permissible rotation
speeds when using the Sticky Stuff adhesive matting, see chapter
5.1.3 "Tray with Sticky Stuff", page 63.
12.4.2 Temperature Parameter (Heating and Ventilation)
Description
Value
Unit
Power heating
800
W
Setting range
4.0 to 65.0
°C
Increment
0.1
°C
Lowest temperature
(above ambient temperature, without op-
tional cooling)
10.0
°C
Highest temperature
65.0
°C
Control precision 4 50 °C
± 0.3
°C
Control precision > 50 °C
± 0.5
°C
Sensor type Pt100 class 1/3 DIN B
Measurement range of the sensor
0 to 80.0
°C
Ventilation 4 axial fans, 24 VDC
Air circulation
450
m
3
/h
12.5 Specifications of the Options
The following section summarises all important technical data and
specification relating to the options.
12.5.1 Internal Cooling
Cooling unit 900 W
Electrical data
Description Type 230 V Type 115 V Unit
Value
Max. power consumption
1
540 540 W
Max. current consumption 4.2 8.4 A
Fuses (5 x 20 mm, slow-blown) 10 - A
Thermal protection switch - 15 A
1
) Power consumption of the compressor

Table of Contents

Related product manuals