CONCEPT IQ. Installation & Programming Manual.
Install
p5
T2. “TAMP”. Dedicated Cabinet Tamper
input. Tamper switch supplied.
No End-of-line resistors necessary.
T6 and T7. Zone Input connections.
Single End-of-Line.
e.g.
3k3 Seal
Open Cct: Alarm
Dual End-of-Line.
e.g.
3k3 Seal
10k1 Alarm
Open Cct: Tamper
Short Cct: Tamper
Zone Doubling.
1k Seal
4k3 1st Zone in Alarm
7k8 2nd Zone in Alarm
11k1 1st & 2nd Zones in Alarm
Open Cct: Tamper
Short Cct: Tamper
T5. “DET+” and “0V”.
Detector Power connections.
12V Supply for Detectors and Auxiliary
Devices. Total combined current sourced
from “DET+” and “LAN+” must not exceed
600 milliAmps.
F1. Battery Input Fuse. 1A. M205.
Connection Details. Detectors, Tamper switch and Fuses
Minimum Cable spec: 14/0.2
Tamp.
Alarm
Detector
C
NC
C
NC
EOL Res.
3k3 Typ.
Tamp.
Alarm
Detector
C
NC
C
NC
EOL Res.
3k3 Typ.
6k8 Typ.
Tamp.
Alarm
2nd Detector
C
NC
C
NC
EOL
1k
6k8
Tamp.
Alarm
1st Detector
C
NC
C
NC
EOL
3k3
PSTN
Line
604 Socket
to other equipment.
604 Cable from
Concept IQ
(Supplied)
Mode 3 Telephone Socket Wiring for Australia
F2. PWR Fuse. 1A. M205.
1
2
3
4
1
2
3
4
5
6
5
6
1
2
5
6
3
4
JP9
Control
Module
1
2
5
6
NOTE: Zone Input connections.
“Normally Open” Alarm Contacts.
Normally Open Alarm Contacts (e.g. As
often found on Smoke Detectors) are
wired in the same manner as Normally
Closed contacts.
When programming the Zone Input,
Option 8 (“Normally Open”) in the “Zone
Options” must be selected. (Addresses
752 [Zone 1] to 767 [Zone 16] )
Control Module. Version 1.02
NOTE:
The 1k EOL
Resistor must
be fitted at the
2nd Detector.