Advisor Advanced ATSx000A(-IP) Installation and Programming Manual  115 
The warning timer can be programmed from 1 to 15 minutes. 
5.n.5 Prealarm time 
 
Every area has its own prealarm timer. When an alarm is triggered, it only 
generates a local alarm, and the prealarm timer is started. If the local alarm is not 
acknowledged during the prealarm time, the alarm is reported. 
Note: The entry zone must have activated option “4.1.n.6.13 Extend EE” 
described on page 99. 
Use the PreAlarm time screen to set the prealarm time for the area. Each area 
can be programmed with one prealarm time. 
The prealarm timers can be programmed from 0 to 255 seconds. 
Note: If zones are assigned to more then one area, the longest prealarm time is 
used. See “4 Zones and RF fobs” on page 94. 
5.n.7 Entry alarms 
 
The Entry alarms option defines whether the entry fail alarm is reported 
immediately. The following values are applicable: 
•  Delayed: The alarm activates 30 s after the entry time passed.  
•  Instant: The alarm activates immediately.  
5.n.8 Autoset retry 
 
Set retry defines whether users can postpone or cancel an autoset. If this option 
is set to On, you can postpone autoset during the Warning time (see “5.n.4 
Warning time” on page 114). If the autoset has been postponed by a normal 
user, the system will attempt autoset again after a time period defined in “8.4.7 
AS user retry” on page 151. 
Note: The privileged users, Installer and Supervisor, can choose the postpone 
time during the Warning time. 
5.n.9 Silent set 
 
If Silent set is on, the keypad buzzer remains silent during the “5.n.4 Warning 
time” described on page 114.