Advisor Advanced ATSx000A(-IP) Installation and Programming Manual 237
Options affected by EN 50131 regulations
EN 50131 Grade 2
Required settings
The following options and values are mandatory for EN 50131-1 Grade 2
regulations.
• 1.2.6.n.2 Period / Time, 24 h for every path to meet ATS Class 2, 4 h for the
IP path to meet ATS Class 4.
• 2.2.1.n.3.3 View areas and 2.2.1.n.3.4 Control areas settings are identical
• 2.2.1.n.3.8 Buzzer silent, never
• 2.2.1.n.3.9 Quick set, off
• 2.2.1.n.3.10 Function keys, all set to None
• 2.2.1.n.3.15 ACK on keypad, set to None for non-LCD keypads
• 3.1.n.7.3 SMS control, disabled for all users
• 3.2.n.5 User group options, 25. No OP/CL reports option set to No
• 4.1.n.6.1 Inhibit, set to No for all zones with type 5. Panic, 6. 24H
• 4.1.n.6.5 Swinger shunt, set to Yes for all zones
• 4.1.n.6.25 ACK on keypad, set to None for all zones with type 9. Keyswitch
• 5.n.3 Entry time, 45 s maximum
• 5.n.7 Entry alarms, Instant
• 7.5.n.2 Active, set to No for all schedules.
• 8.1.2.1 Activation, external siren 90 to 900 s
• 8.1.2.2 Delay time, external siren 600 s maximum
• 8.1.3.1 Armed display, 30 s maximum
• 8.1.3.4 Mains reporting delay, 3600 s maximum
• 8.2.1 User code required, enabled
• 8.3.1 Armed display, always
• 8.3.3 Alarm list, disabled
• 8.4.1 RTS options, all enabled except zone technical alarm, which is optional
• 8.4.2 Inhibit includes, all allowed except engineer reset, which must be
disabled
• 8.4.5 Pending alarms, enabled
• 8.5.4 Swinger shunt ≥ 3
• 8.5.5 Report restore, on ACK
• 9.3.n.2 Line fault, enabled per path used
• 9.3.n.3 Line fault delay, 0 s
It is required to apply the following supervision settings for wireless DGPs:
• Short supervision: 20 minutes
• Long supervision: 2 hours
• Smoke supervision: 4 hours
Refer to appropriate sections and manuals.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Interlogix Advisor Advanced ATS2000A-MM and is the answer not in the manual?

Interlogix Advisor Advanced ATS2000A-MM Specifications

General IconGeneral
BrandInterlogix
ModelAdvisor Advanced ATS2000A-MM
CategoryControl Panel
LanguageEnglish

Related product manuals