234  Advisor Advanced ATSx000A(-IP) Installation and Programming Manual 
Example: Panel tampers. 
8. Exit terminator 
This zone type is used to terminate an exit time. If the zone switches from active 
to normal, the exit time is terminated and the area(s) are completely set as soon 
as the final set delay has expired (see also “8.1.3.5 Final set delay” on page 
140”). 
9. Keyswitch 
When the zone switches, the area is set / unset / part set depending on the zone 
options selected.  
Example: Key switch next to Front door.  
See options “4.1.n.6.15 Key latch” on page 99, “4.1.n.6.16 Key set” on page 100, 
“4.1.n.6.17 Key unset” on page 100. 
10. Medical 
Generates a medical alarm regardless of the status of the area.  
11. Technical 
Generates a technical alarm regardless of the status of the area.  
Example: temperature sensor. 
See options “4.1.n.6.18 Technical full set” on page 100, “4.1.n.6.19 Technical 
unset” on page 100. 
12. Transmission path fault 
Monitors the external reporting device.  
13. Fire door 
If there is no fire alarm present, generate an intrusion alarm regardless of the 
status of the area. Otherwise no intrusion alarm is generated. 
Example: Fire doors or emergency doors. 
See also “4. Fire” on page 233. 
14. Aux mains fault 
Monitors the auxiliary mains supply.  
15. Aux batt fault 
Monitors battery of the auxiliary power supply.  
16. Key box 
Monitors a box that holds a key to premises. It allows you to open for a short 
period after setting an area (specified in key box timer, see “8.1.4.5 Key box 
time” on page 142). It generates an alarm when opened outside of this period.