Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
The communication address of the drive is unique
the communication net. This
the point to point communication between the upper
monitor and the drive.
Note: The address of the slave cannot set to 0.
P14.01
Set the digital transmission speed between the
upper monitor and the inverter.
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
Note: The
baud rate between the upper monitor and
the inverter must be the same. O
communication is not applied. T
rate, the quicker the communication speed.
4 ○
P14.02
data format between the upper monitor and the
inverter must be the same. O
communication is not applied.
0: No check (N,8,1)for RTU
1:Odd check (E,8,1)for RTU
2:Even check (O,8,1)for RTU
3:No check (N,8,2)for RTU
4: Odd check (E,8,2)for RTU
5:Even check(O,8,2)for RTU
1 ○
P14.03
Answer
delay
0~200ms
It means the interval time between the interval
when the drive receive the data and sent it to the
f the answer delay is shorter than the
system processing time, then the answer delay