Goodrive200 inverters Function codes
114
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
The communication address of the drive is unique
in
the communication net. This
is the fundamental for
the point to point communication between the upper
monitor and the drive.
Note: The address of the slave cannot set to 0.
P14.01
C
ommunicati
baud ratio
Set the digital transmission speed between the
upper monitor and the inverter.
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
Note: The
baud rate between the upper monitor and
the inverter must be the same. O
therwise, the
communication is not applied. T
he bigger the baud
rate, the quicker the communication speed.
4
P14.02
Digital bit
checkout
The
data format between the upper monitor and the
inverter must be the same. O
therwise, the
communication is not applied.
0: No check (N,8,1)for RTU
1:Odd check (E,8,1)for RTU
2:Even check (O,8,1)for RTU
3:No check (N,8,2)for RTU
4: Odd check (E,8,2)for RTU
5:Even check(O,8,2)for RTU
1
P14.03
Answer
delay
0~200ms
It means the interval time between the interval
time
when the drive receive the data and sent it to the
upper monitor. I
f the answer delay is shorter than the
system processing time, then the answer delay
time
5