Goodrive200 inverters Function codes
115
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
is the system processing time, if the answer delay is
longer than the system processing time,
then after
the system deal with the data, waits
until achieving
the answer delay time to send the data to the upper
monitor.
P14.04
Fault time
of
communicati
on overtime
0.0(invalid),0.1~60.0s
When the function code is set as 0.0
, the
communication overtime parameter is invalid.
When the function code is set as non-
zero, if the
interval time between two communications exceed
s
the communication
overtime, the system will report
“485 communication faults” (CE).
Generally, set it as invalid;
set the parameter in the
continuous communication
to monitor the
communication state.
0.0s
P14.05
Transmissio
n fault
processing
0:Alarm and stop freely
1:No alarm and continue to run
2:
No alarm and stop according to the stop
means(only under the communication control)
3:
No alarm and stop according to the stop
means(under all control modes)
0
P14.06
Communicati
on
processing
0x00~0x11
LED ones:
0: Operation with response: the
drive will respond to
all reading and writing commands of the upper
monitor.
1:Operation without response The
drive only
responds to the reading command
other than the
writing
command of the drive. The communicatio
n
efficiency can be increased by this method.
LED tens:(reserved)
0x00