EasyManua.ls Logo

INVT Goodrive 200 - Page 163

INVT Goodrive 200
253 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive200 inverters Basic operation instruction
162
Goodrive200 series inverters have 2 relay output terminals and 1 open-collector output terminal
and 1 high speed pulse output terminal in the standard configuration. All functions of the digital
input terminals are programmable by the function codes. Open collector pole output can be
selected into high speed pulse input terminal or common switch input terminal by function code.
The below table is the option of the four function parameters and selecting the repeated output
terminal function is allowed.
Set value
Function Instructions
0 Invalid The output terminal has no function.
1 Running
Output ON signal when the inverter is running and
there is frequency output.
2 Forward running
Output ON signal when the inverter is running
forward and there is frequency output.
3 Reverse running
Output ON signal when the inverter is running
reverse and there is frequency output.
4 Jogging
Output ON signal when the inverter is jogging and
there is frequency output.
5 Inverter fault Output ON signal when the inverter is in fault
6 FDT1
Please refer to P08.32 and P08.33 for detailed
information.
7 FDT2
Please refer to P08.34 and P08.35 for detailed
information.
8 Frequency arrival Please refer to P08.36 for detailed information.
9 Zero-speed running
Output ON signal when the output frequency and
reference frequency of the inverter is 0 at the same
time.
10 Upper-limit frequency arrival
Output ON signal when the running frequency of the
inverter is the upper limit frequency.
11 Upper-limit frequency arrival
Output ON signal when the running frequency of the
inverter is the lower limit frequency.
12 Ready
When the main circuit and the control circuit is
established and the protection function of the
inverter is not active. The inverter is in the running
state and it will output ON signal.

Table of Contents

Related product manuals