Description
24V
The inverter provides the power supply for users with a maximum
output current of 200mA
HDO
1. Switch input:200mA/30V
2. Output frequency range:0~50kHz
CME
Common terminal of HDO and Y1, short-connected with COM in
factory
Y1
1.Swtich capability:200mA/30V
2.Output frequency range:0~1kHz
COM +24V common terminal, short-connected with CEM in factory
485+
485-
485 communication interface and 485 differential signal interface
If it is the standard 485 communication interface, please use
twisted pairs or shield cable.
PE Grounding terminal
4.3.6 Input /Output signal connection figure
Please use U-shaped contact tag to set NPN mode or PNP mode and the internal or external
power supply. The default setting is NPN internal mode.
Fig 4-21 U-shaped contact tag