Goodrive200 inverters Installation guidelines
RO1 relay output, RO1A NO, RO1B NC, RO1C common terminal
Contactor capability: 3A/AC250V,1A/DC30V
RO2A
RO2 relay output, RO2A NO, RO2B NC, RO2C common terminal
Contactor capability: 3A/AC250V,1A/DC30V
Terminal
PE
Grounding terminal
PW
Provide the input switch working power supply from external to
internal.
Voltage range: 12~24V
24V
The inverter provides the power supply for users with a maximum
output current of 200mA
COM +24V common terminal
S1 Switch input 1
S2 Switch input 2
S3 Switch input 3
S4 Switch input 4
S5 Switch input 5
S6 Switch input 6
S7 Switch input 7
S8 Switch input 8
1. Internal impedance:3.3kΩ
2. 12~30V voltage input is available
3. The terminal is the dual-direction input
terminal supporting both NPN and PNP
4. Max input frequency:1kHz
5. All are programmable digital input
terminal. User can set the terminal function
through function codes.
, this terminal can be used as high frequency