Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
lower than
the lower
limit one
(valid if the
lower limit
function code determines the running state of
the inverter when the set frequency is lower than the
lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
T
he inverter will coast to stop when the set
frequency is lower than the lower-
frequency is above the lower limit one again and it
lasts for the time set by P01.20, the inverter will
come back to the running state automatically.
0 ◎
P01.20
his function code determines the Hibernation delay
hen the running frequency of the inverter is
lower than the lower limit one, the inverter will pause
to stand by.
When the set frequency is above the lower
again and it lasts for the time set by P01.20, the
inverter will run automatically.
Note: T
he time is the total value when the set
frequency is above the lower limit one.
Setting range: 0.0~3600.0s (valid when P01.19=2)
his function can enable the inverter start or not after
the power off and then power on.
0: Ddisable
1: Enable
, if the starting need is met, the inverter will