Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
Setting range: 0.0~3600.0s
P01.14
Shifting
between
FWD/REV
rotation
Set the threshold point of the inverter:
0:Switch after 0 frequency
1:Switch after the starting frequency
0 ◎
P01.15
running
protection
when
powering on
When the running command channel is the terminal
control, the system will detect the state of the
running terminal during powering on.
0: The terminal running command
powering on. Even the running
to be valid during powering on, the inverter won’
in the protection state until the
running command is canceled and enabled again.
1: The terminal running command
powering on. If the running
be valid during powering on, the system will start the
inverter automatically after the initialization.
Note:
this function should be selected with cautions,
or serious result may follow.
0 ○