Goodrive200 inverters Function codes
58
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range: 0.0~3600.0s
P01.14
Shifting
between
FWD/REV
rotation
Set the threshold point of the inverter:
0:Switch after 0 frequency
1:Switch after the starting frequency
0
P01.15
Stopping
speed
0.00~100.00Hz 0.10 Hz
P01.16
Reserved
0
P01.17
Reserved
0.05s
P01.18
Terminal
running
protection
when
powering on
When the running command channel is the terminal
control, the system will detect the state of the
running terminal during powering on.
0: The terminal running command
is invalid when
powering on. Even the running
command is detected
to be valid during powering on, the inverter won’
t run
and the system keeps
in the protection state until the
running command is canceled and enabled again.
1: The terminal running command
is valid when
powering on. If the running
command is detected to
be valid during powering on, the system will start the
inverter automatically after the initialization.
Note:
this function should be selected with cautions,
or serious result may follow.
0