Goodrive200 inverters Function codes
57
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
P01.11
DC braking
current
0.0%
P01.12
DC braking
time
prevent over-
current fault caused by DC braking at
high speed.
DC braking current
The value of P01.11 is the
percentage of rated current of inverter. The bigger
the DC braking current is
, the greater the braking
torque is.
DC braking time: The retention
time of DC brake. If
the time is 0, the DC brake is invalid. The inverter will
stop at the set deceleration time.
Setting range of P01.09: 0.00 Hz
~P00.03 (the Max.
frequency
Setting range of P01.10: 0.0~50.0s
Setting range of P01.11: 0.0~150.0%
Setting range of P01.12: 0.0~50.0s
0.0s
P01.13
Dead time of
FWD/REV
rotation
During the procedure of switching FWD/REV
rotation, set the threshold by
P01.14, which is as the
table below:
0.0s