Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
The setting range of P01.03: 0.0~150.0%
The setting range of P01.04: 0.0~50.0s
P01.05
The changing mode of the frequency during start-
and running.
0:Linear type
The output frequency increases or decreases
Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to decrease
the output frequency during the set time. When the
frequency decreases to 0Hz, the inverter stops.
1: Coast to stop: after the stop command bec
valid, the inverter ceases the output immediately.
And the load coasts to stop at the mechanical inertia.
Starting frequency of DC braking: start the DC
braking when running frequency reaches starting
frequency determined by P1.09.
Waiting time before DC braking: Inverters block the
output before starting the DC brak
waiting time, the DC braking will be started so as to