Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
original frequency during the inverter starting. See
P01.02 for detailed information.
Setting range: 0.00~50.00Hz
P01.02
Retention
time of the
starting
frequency
Set a proper starting frequency to increase the
torque of the inverter during starting. During the
retention time of the starting frequency, the output
frequency of the inverter is the starting frequency.
And then, the inverter will run from the
frequency to the set frequency. If the set frequency is
lower than the starting frequency, the inverter will
stop running and keep in the stand-
starting frequency is not limited in the lower limit
frequency.
Setting range: 0.0~50.0s
0.0s ◎
P01.03
The braking
current
before
starting
0.0%
The braking
time before
starting
The inverter will carry out DC braking at the braking
current set before starting and it will speed up after
the DC braking time. If the DC braking time is set to
0, the DC braking is invalid.
The stro
nger the braking current, the bigger the
braking power. The DC braking current before
starting means the percentage of the rated