Goodrive270 series VFD for fan and pump Basic operation guidelines
-97-
Present
reference
channel
P00.09
Multifunction
terminal function 13
(Switch from
channel A to channel
B)
Multifunction
terminal function 14
(Switch from
combined setting to
channel A)
Multifunction
terminal function 15
(Switch from
combined setting to
channel B)
A+B
/
A
B
A-B
/
A
B
Max(A, B)
/
A
B
Min(A, B)
/
A
B
Note: "/" indicates this multifunction terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the VFD via multi-function terminal UP (10) and DOWN
(11), you can increase/decrease the frequency quickly by setting P08.45 (UP terminal frequency
incremental change rate) and P08.46 (DOWN terminal frequency decremental change rate).
Sx
Sy
UP terminal
function selection=10
DOWN terminal
function selection=11
UP terminal state
DOWN terminal state
T
F
T
T
UP terminal frequency incremental integral speed P08.45
DOWN terminal frequency decremental integral speed P08.46
Related parameter list:
Function
code
Name
Description
Default
P00.03
Max. output frequency
P00.04400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz P00.04
0.00Hz
P00.06
Setting channel of A
frequency command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Simple PLC program
0
P00.07
Setting channel of B
frequency command
15