EasyManua.ls Logo

janitza UMG 96 RM-E - Page 101

janitza UMG 96 RM-E
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
101
UMG 96RM-E
Current measurement I1 - I4
Rated current 5A
Measurement range 0 .. 6A
rms
Crest factor 1.98
Resolution 0.1mA (Display 0.01A)
Overvoltage category 300V CAT II
Measurement surge voltage 2kV
Power consumption approx. 0.2 VA (Ri=5mOhm)
Overload for 1 sec. 120A (sinusoidal)
Sampling frequency 20kHz
Residual current measurement I5 / I6
Rated current 30mA
rms
Measurement range 0 .. 40mArms
Operating current 50µA
Resolution 1µA
Crest factor 1.414 (related to 40mA)
Burden 4 Ohm
Overload for 1 sec. 5A
Sustained overload 1A
Overload for 20 ms 50A
Residual current measurement i.a.w. IEC/TR 60755 (2008-01), Type A
Type B

Table of Contents

Other manuals for janitza UMG 96 RM-E

Related product manuals