Figure 58: Breckman printer
Control center setup
Chiller ID
Access level required: operator
Using the COMMS Screen, assign an identification number to the chiller. This number will appear
atthe top of each report.
Printer setup
Access level required: operator
Using the COMMS Screen, the Control Center must be configured to transmit data in the same
format as the printer is configured to receive the data. The following values must be entered.
Baud Rate - Set to 9600 for Brecknell 19200 for OKIPOS
Data Bits - 8
Parity - None
Stop Bits - 1
Printer type
Access level required: operator
Using the PRINTER Screen, set the printer type to Weigh-Tronix.
Automatic data logging
Access level required: operator
If automatic data logging is desired, a status report can be automatically printed at a specified
interval beginning at a specified time, using the PRINTER Screen. The interval is programmable
over the range of 1 minute to 1440 minutes in 1 minute increments. The first print will occur at
the programmed START time and occur at the programmed Output Interval thereafter. The time
remaining until the next print is displayed on the PRINTER Screen.
Automatic Printer Logging - Enables and disables automatic data logging.
Log Start Time - Enter the time the first print is desired.
Output Interval - Enter the desired interval between prints.