EasyManua.ls Logo

Johnson Controls YORK YMC2 - Page 27

Johnson Controls YORK YMC2
184 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 6: Water flow rate limits in GPM (LPM) – based upon standard tubes at design full load
conditions
Evaporator Condenser
1 pass 2 pass 3 pass 1 pass 2 pass 3 pass
Evaporator model
Min Max Min Max Min Max
Condenser model
Min Max Min Max Min Max
EC3914-3
1960
(50)
7850
(198)
980
(25)
3930
(99)
650
(16)
2500
(66)
CB2912-3
2020
(163)
7270
(588)
1010
(81)
3630
(294)
EC3914-4
2560
(50)
10250
(198)
1280
(25)
5120
(99)
850
(16)
3190
(66)
CB3314-B
1750
(163)
6310
(588)
880
(81)
2820
(294)
580
(54)
1890
(196)
EC3914-5
2860
(50)
11430
(198)
1430
(25)
5720
(99)
CB3314-C
2060
(163)
7420
(588)
1030
(81)
3250
(294)
690
(54)
2200
(196)
CB3314-D
2650
(163)
9540
(588)
1320
(81)
3990
(294)
880
(54)
2790
(196)
CB3314-E
2920
(163)
10540
(588)
1460
(81)
4310
(294)
CB3314-2
1940
(163)
7000
(588)
970
(81)
3500
(294)
650
(54)
2330
(196)
CB3314-3
2250
(163)
8120
(588)
1130
(81)
4060
(294)
750
(54)
2710
(196)
CB3314-4
2910
(163)
10490
(588)
1450
(81)
5120
(294)
CB3914-B
2840
(163)
10220
(588)
1420
(81)
4210
(294)
950
(54)
2970
(196)
CB3914-C
3210
(163)
11580
(588)
1610
(81)
4610
(294)
1070
(54)
3330
(196)
CB3914-D
3540
(163)
12740
(588)
1770
(81)
4930
(294)
CB3914-2
2650
(163)
9550
(588)
1330
(81)
4780
(294)
880
(54)
3180
(196)
CB3914-3
3160
(163)
11390
(588)
1580
(81)
5390
(294)
1050
(54)
3800
(196)
CB3914-4
3770
(163)
13580
(588)
1880
(81)
5960
(294)
27