NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING
JURISDICTION AND ALL OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard Control Units and Accessories for Fire Alarm Systems, ANSI/UL 864, certain
programming features or options must be limited to specific values or not used at all as indicated below.
Abort switches may be set-up to operate in any of the following ways:
1. Abort Mode 1
*
(UL) - Count down to 10 seconds and hold. Resume countdown at 10 seconds.
2. Abort Mode 2 (Reset) - Reset to initial delay setting. Resume countdown for entire delay period.
3. Abort Mode 3 (IRI) - Same as Mode 1, except disable abort function if countdown timer has started.
4. Abort Mode 4 (NYC) - Resets to 120 seconds.
5. Abort Mode 5 - Disables the abort.
*
Only Abort Mode 1 is ANSI/UL 864 compliant.