Appendix C: Applications
P/N 3102351-EN • REV 005 • ISS 28DEC18 225
Notes
For PS/PD, PHS/PHD, IPHS, and SD detectors configured as “Supervisory Non-latching”
device type or for PCOS/PCD detectors (smoke element) configured as “Smoke
Supervisory Non-latching” device type, if the base is Relay/Sounder, then the follow type
option cannot be configured as “Head.” The follow type in this case should be set to
“Alarm.”
The following procedure must be done using the Configuration Utility (CU).
To program the sounder base for T3T4 Fire/CO:
1. Set the panel’s Event Notification option to Device/Zone.
2. Configure the detectors as follows:
Message Line 1: DETECTOR_<N>, where <N> can be the device address or other number
Device Type: Primary sensor type + CO alarm
Base Type: SBT/ABDT Sounder
Follow: None, Head, Alarm, Alm + Vrfy, or Alm + PreAlm
Follow CO: No or Yes (only displays if Follow is set to Alarm, Alm + Vrfy, or Alm + PreAlm)
3. Configure the RM1 or CT1 module as follows:
Device type: Monitor
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_RLY_1
4. Configure Correlation Group 001 as follows:
Add/Remove Zone: As required
Add/Remove NAC: As required
Add/Remove Device: Add all alarm signal initiating devices corresponding T3T4 device
Channels as described below
To create correlations for T3T4:
1. Channel 1 must be correlated with proper SBT/ABDT sounder base as output to any
primary alarming type inputs.
2. Channel 2 can be correlated with proper SBT/ABDT sounder base as output to secondary
element (CO) of GSA detectors.
3. If both Channel 1 and Channel 2 are correlated as outputs to a sounder base, then
Channel 1 pattern overwrites the Channel 2 pattern.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217