Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 55
Description
Smoke verified + CO monitor
latching
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
a monitor latching event (CO).
Smoke verified + CO monitor
nonlatching
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
a monitor nonlatching event (CO).
Photoelectric smoke/heat and CO detectors (PHC
D)
For heat and smoke + CO detectors that trigger an active alarm event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset. [1]
Smoke/Heat + CO monitor
latc
hing
For heat and smoke + CO detectors that trigger an active alarm event (smoke or
heat) or a CO latching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset. [1]
Smoke/Heat + CO monitor
nonlatching
For heat and smoke + CO detectors that trigger an active alarm event (smoke or
heat) or a CO nonlatching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the
smoke/heat type event. Resetting the control panel is not required for monitor
nonlatching. [1]
Smoke/Heat + CO supervisory
latching
For heat and smoke + CO detectors that trigger an active alarm event (smoke or
heat) or a CO latching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset. [1]
Smoke/Heat + CO supervisory
nonlatching
For heat and smoke + CO detectors that trigger an active alarm event (smoke or
heat) or a CO nonlatching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the
smoke/heat type event. Resetting the control panel is not required for supervisory
nonlatching. [1]
Smoke verified + CO alarm
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
an active alarm event (CO). [1]
Smoke verified + CO
supervisory latching
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
a supervisory latching event (CO). [1]
Smoke verified + CO
supervisory nonlatching
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
a supervisory nonlatching event (CO). [1]
Smoke verified + CO monitor
latching
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
a monitor latching event (CO). [1]