Chapter 2: Front panel programming
54 P/N 3102351-EN • REV 005 • ISS 28DEC18
Description
Smoke supervisory latching +
CO monitor latching
For smoke + CO detectors that trigger a supervisory latching event (smoke) or
monitor latching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.
Smoke supervisory latching +
CO monitor nonlatching
For smoke + CO detectors that trigger a supervisory latching event (smoke) or a
monitor nonlatching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for monitor nonlatching.
Smoke supervisory
nonlatching + CO alarm
For smoke + CO detectors that trigger a supervisory nonlatching event (smoke)
or an active alarm event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the CO type
event. Resetting the control panel is not required for supervisory nonlatching.
Smoke supervisory
nonlatching + CO supervisory
latching
For smoke + CO detectors that trigger a supervisory nonlatching event (smoke)
or a supervisory latching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the CO type
event. Resetting the control panel is not required for supervisory nonlatching.
ching + CO supervisory
For smoke + CO detectors that trigger a supervisory nonlatching event (smoke or
CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is not required for supervisory
nonlatching.
Smoke supervisory
nonlatching + CO monitor
latching
For smoke + CO detectors that trigger a supervisory nonlatching event (smoke)
or a monitor latching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the CO type
event. Resetting the control panel is not required for supervisory nonlatching.
Smoke supervisory
nonlatching + CO monitor
nonlatching
For smoke + CO detectors that trigger a supervisory nonlatching event (smoke)
or a monitor nonlatching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is not required for monitor
nonlatching.
Smoke verified + CO alarm
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
an active alarm event (CO).
CO
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
a supervisory latching event (CO).
Smoke verified + CO
superviso
ry nonlatching
For smoke + CO detectors that trigger an alarm verify event first, and then trigger
an active alarm event only after confirming the alarm condition (smoke) or trigger
a supervisory nonlatching event (CO).