Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 53
Device type
Description
Supervisory nonlatching
For detectors that trigger an active supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is not required.
Photoelectric smoke and CO dete
ctors (PCOS/PCD)
Smoke Alarm + CO alarm
For smoke + CO detectors that trigger an active alarm event (smoke or CO).
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke
alarm + CO monitor
latching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
latching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke alarm + CO monitor
nonlatching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
nonlatching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for monitor nonlatching.
Smoke alarm + CO
supervisory latching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
latching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke alarm + CO
supervisory nonlatching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
nonlatching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for supervisory
nonlatching.
Smoke supervisory latching +
CO alarm
For smoke + CO detectors that trigger a supervisory latching event (smoke) or an
active alarm event (CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.
Smoke supervisory latching +
CO supervisory latching
For smoke + CO detectors that trigger a supervisory latching event (smoke or
CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.
Smoke supervisory latching +
CO supervisory nonlatching
For smoke + CO detectors that trigger a supervisory latching event (smoke) or a
supervisory nonlatching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for supervisory
nonlatching.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217

Related product manuals