Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 53
Description
For detectors that trigger an active supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is not required.
Photoelectric smoke and CO dete
ctors (PCOS/PCD)
For smoke + CO detectors that trigger an active alarm event (smoke or CO).
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
alarm + CO monitor
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
latching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke alarm + CO monitor
nonlatching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
nonlatching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for monitor nonlatching.
Smoke alarm + CO
supervisory latching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
latching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke alarm + CO
supervisory nonlatching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
nonlatching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for supervisory
nonlatching.
Smoke supervisory latching +
CO alarm
For smoke + CO detectors that trigger a supervisory latching event (smoke) or an
active alarm event (CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.
Smoke supervisory latching +
CO supervisory latching
For smoke + CO detectors that trigger a supervisory latching event (smoke or
CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.
Smoke supervisory latching +
CO supervisory nonlatching
For smoke + CO detectors that trigger a supervisory latching event (smoke) or a
supervisory nonlatching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for supervisory
nonlatching.