d3.25
Analog2_Filter
Used to smooth the input analog signals.
Filter frequency: f=4000/(2π*
Analog1_Filter)
Time Constant (T) = Analog2_Filter/4000
(S)
5
1~127
d3.26
Analog2_Dead
Sets dead zone data for external analog
signal 2
0
0~8192
d3.27
Analog2_Offset
Sets offset data for external analog signal 2
0
-8192~8
192
d3.28
Analog_Speed_Con
Selects analog-speed channels
0: Invalid analog channel
1: Valid analog channel 1 (AIN1)
2: Valid analog channel 2 (AIN2)
Valid mode -3 and mode 3
0
N/A
d3.29
Analog_Speed_Factor
Sets the proportion between analog signals
and output speed
1000
N/A
d3.32
Analog_MaxT_Con
0: No control
1: Max torque that Ain1 can control
2: Max torque that Ain2 can control
0
N/A
d3.33
Analog_MaxT_Factor
Indicates the max torque factor for analog
signal control
8192
N/A
7.2.3 Analog Signal Processing
Fig. 7-6 Analog signal processing
Electrical control on internal variables is available only after ADC conversion and offset of external analog
signals, and judgment of dead zone signals.
For offset processing, see the left part in Fig. 7-6; for dead zone processing, see the right part in Fig. 7-6.
Mathematical equation for offset processing:
shiftexternalernal
UUU
int
2047
-2048
shift
U
-10v
10v
1
0
2047
-2048
2
dead
U
-10v
10v
external
U
external
U
ernal
U
int
ernal
U
int
Offset
Dead zone