199
MA06-03-1-01
Menu
- Defective connection
- Magnetic tape not installed correctly (Installation manual!)
- Defective travelling cable
- Defective CPU
Remedy
- See causes
- Check landing heights (Menu -> Setup)
Error code : 37
Reset
Automatic
Short text
Undershoot lowest floor
Long text
Undershoot or reference level not correct
Description
The value determined by the absolute encoder does not coincide with the reference value for the highest
landing which is determined by the controller (zero-point)
Reaction
General
The controller switches into “out-of-order” mode.
Rope
The controller initiates an emergency stop.
Hydraulic
The controller initiates an emergency stop and descends into the lowest landing.
Causes
- Reading error of the absolute encoder
- Defective connection
- Magnetic tape not installed correctly (Installation manual!)
- Defective travelling cable
- Defective CPU
Remedy
- See causes
- Check zero point (Menu -> Setup)
Error code : 38
Reset
800 + Ok / Recall / By entering a car call
Short text
Door 1 did not close
Long text
Door 1 did not close after 5 retry
Description
The controller initiated 10 attempts for closing, during all of which the safety cicuit failed to successfully
close given the predetermined control time for the closing of doors.
Reaction
General
The controller switches into “out-of-order” mode.
Rope
Hydraulic
Causes
- defective interlocking contact
- defective door contact
- control time for closing doors is set too restrictively
- door motor has too little contact pressure
Remedy
- See causes
Error code : 39
Reset
Input Reset Earthquake (Parameter -> Mode -> Operation mode 4/4 -> Earthquake ->I:Reset xxx )
Short text
Seismic Device 24H
long text
Seismic Device 24H test not ok
Description
The controller checks the seismic device every 24 hours automatically so that the Earthquake function
is ensured. This error message will be issued, should the controller detect an error.
Reaktion
The controller switches into “out-of-order” mode.
Ursachen
- Failure or disruption at the seismics detector
- Output/Input at the controller is defective
Beseitigung
- Check seismics detector
- Check wiring