- Check output test seismic and input seismic mode
The lead-battery which is mounted to the controller is either defective or not connected (is only checked
in standstill)
The controller switches into “out-of-order” mode.
The lift stops in the current landing
The lift descends into the lowest landing
- battery disconnected
- defective battery
- See causes
If the battery should be defective, one deactivates the monitoring via the menu “Tools ->
Adjustment -> Surveillance -> Battery control j/n”
We highly URGE you to note that the battery needs to be replaced both at your installation and
in the maintenance book.
This error code indicates that there has been a brake error prior to reset or restart.
The control switches into “out-of-order” mode.
- A brake error that existed prior to shut-down/reset was saved
- Remove the brake error as indicated under error code 43-46 and reset with 800+OK
The integrated phase sequence detects a phase failure or a wrong direction of rotation.
The controller switches into “out-of-order” mode.
The lift stops in the current landing
The lift descends into the lowest landing
- Phase failure in the mains
- Phases are not clamped correctly L1/L2/L3
- Defective fuse in the controller/allocation
- See causes
If the phase sequence monitoring is not needed, one can deactivate the monitoring via the
menu “Tools -> Adjustment -> Surveillance -> Phase control j/n”
We highly URGE you to note this circumstance both at your installation and in the maintenance
book.