53
MA06-03-1-01
Menu
The deceleration control circuit monitors the approaching speed when arriving at the last landings. For
this purpose, there is a deceleration-control point installed at both upper are and bottom of the shaft.
At those points, the approaching speed is required to be less than a predetermined value.
If this deceleration cannot be performed, an emergency stop will be affected due to this error.
[Direct access: CMD -> 7207]
Parameter
[Direct access]
Description
Default
value
Value Range
Speed limit(mm/s)
Setting of the maximum permissible speed
at the deceleration control point.
0-9999 mm/s
O:Speed<Speed limit
This is the output of the monitoring circuit,
which is active as long as the speed limit is
not being exceeded.
O:Bypass in
acceleration
This is the output of the monitoring circuit.
It enables the deactivation of the
monitoring process when the installation is
accelerating from the final landing.
I:Safety relay monitor
Set an input for the monitoring of the
deceleration control’s safety circuit.
Magnet.switch
monitor
Set an input for the dropout monitoring of
the deceleration control switch and the
associated contactors.