MA06-03-1-01
Menu
[Direct access: CMD -> 7044]
Parameter
[Direct access]
Description
Default
value
Value
Range
T:Door open time (s)
The door-opening check time describes the
time interval provided to the door drive for
opening the door. After the door-opening
check time has elapsed, idle time starts.
15
0-99
T:Door close time (s)
Definition of the door-closing check time
(seconds) which describes the time interval
provided to the door drive for closing the door.
After the door-closing check time has elapsed,
the door opens again.
15
0-99
T:Staytime landing call
(s)
Idle time (=waiting time) when processing
following landing calls.
3
0-99
T:Staytime car call (s)
Idle time (= waiting time) when processing
following car calls.
3
0-99
T:Door close delay (s)
Definition of the door closing delay (in
seconds).
0
0-99
T:Nudging time (s)
Definition of the nudging time (in seconds)
which is allowed to elapse before doors are
forced to close.
0
0-99
t:Door open/close (ms)
Definition of the switching delay between door
open signal and door close signal and vice
versa (in milliseconds).
200
0-9999
Ignore timer with car
call
When this parameter is activated, a car call
causes the idle time to be skipped and initiates
an immediate closing of doors and
continuation of travel.
NO
YES/NO