EasyManua.ls Logo

KMC Controls BAC-4000 series - Page 9

KMC Controls BAC-4000 series
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Short-circuit protected
Loads up to 10 mA at 0–12 volts DC
8-bit PWM digital-to-analog conversion
Relay outputs
Relay outputs are configured to represent BACnet binary objects. The
outputs control on/off valves, speeds for three-speed fans, fan start circuits,
or other equipment that requires an on or off input signal.
All relay outputs are normally open, SPST, Form “A” relays
1 Ampere maximum per relay at 24 volts AC or DC for each output.
Maximum for all relay outputs is 3 amperes (72VA).
Connectors
Screw terminal block mounted to backplate
Wire size 14-22 AWG
CommunicationsBACnet MS/TP
Integral peer-to-peer BACnet MS/TP network communications.
Network speeds from 9600 to 76,800 baud.
Front panel configurable device instance, MAC address, and baud.
Automatic baud detection.
Screw terminal block mounted to backplate. Wire size 14–22 AWG
Meets or exceeds ANSI/ASHRAE BACnet Standard 135-2008 for
Application Specific Controllers
Accuracy–temperature only models
Type Thermistor
Accuracy ±0.36° F (±0. C)
Resistance 10,000 at 77° F (25° C)
Operating range 48 to 96° F (8.8 to 35. C)
Accuracy–temperature and humidity models
Temperature Sensor
Type CMOS
Accuracy ±0. F offset (±0. C) from 40° to 104° F
(4.4 to 40° C)
Resolution ±0.F (±0.1° C)
Operating range 36 to 120° F (2.2 to 48. C)
Response time 5 to 30 seconds
Installation, Operation, and Application Guide for AppStat Section 1: Introduction to the AppStat
Revision G 9

Table of Contents

Related product manuals