KW Aufzugstechnik GmbH OPERATING MANUAL DAVID-613
DAVID-D613-V125-E 13.04.2021 Page - 126 -
B5 Indicate
B501- Car Indicators
General
The car-position of the elevator has two output-devices, namely ZR and ITR. In both of the following
parameters you can choose the output of the car-position:
Parameter Car Indicate ZR - Parameter Car Indicate EIT - Description Remote Station ER
There are always 8 output-channels on both of the two units. You can choose the following codes to
show the car-position: 1 of N-Code, Binary-Code, Graycode, Digits-Indicator and User-defined character
set.
1 of N Code
The 1 of N code always has one output-channel for one floor indicator. When the car is in the first floor
channel 21 h is active ( +24V DC).
All other outputs have 0V DC. Lift systems with 1 until 8 stops can be represented in this way.
If there are more stops used, it must be converted into an encoded representation.
Binary Code
In the binary code, the floors are a combination of some output channels. Active channels have a “1”.
This means that there is a +24V DC level.
Stop
25h
24h
23h
22h
21h
1.Floor
0
0
0
0
1
2.Floor
0
0
0
1
0
3.Floor
0
0
0
1
1
4.Floor
0
0
1
0
0
5.Floor
0
0
1
0
1
6.Floor
0
0
1
1
0
7.Floor
0
0
1
1
1
8.Floor
0
1
0
0
0
9.Floor
0
1
0
0
1
10.Floor
0
1
0
1
0
11.Floor
0
1
0
1
1
12.Floor
0
1
1
0
0
13.Floor
0
1
1
0
1
14.Floor
0
1
1
1
0
15.Floor
0
1
1
1
1
16.Floor
1
0
0
0
0
17.Floor
1
0
0
0
1
Gray Code
In the gray code, the floors are a combination of some output channels. Active channels have a “1”.
This means that there is a +24V DC level.
Stop
25h
24h
23h
22h
21h
1.Floor
0
0
0
0
1
2.Floor
0
0
0
1
1
3.Floor
0
0
0
1
0
4. Floor
0
0
1
1
0
5.Floor
0
0
1
1
1
6.Floor
0
0
1
0
1
7.Floor
0
0
1
0
0
8.Floor
0
1
1
0
0
9.Floor
0
1
1
0
1
10.Floor
0
1
1
1
1
11.Floor
0
1
1
1
0
12.Floor
0
1
0
1
0
13.Floor
0
1
0
1
1
14.Floor
0
1
0
0
1
15.Floor
0
1
0
0
0
16.Floor
1
1
0
0
0
17.Floor
1
1
0
0
1
7-Digits-Indicator
In the 7-Digits-code, the floors are a combination of some output channels. Active channels have a
“1”. This means that there is a +24V DC level.