B605- STANDBY TRAVEL
PARAMETER: STANDBY TRAVEL
In this parameter, you can activate the standby travel. To use the standby-travel, you must put a +24V
DC voltage at the input channel.
Takes place during the rest ride a ride reversing, the door remains closed in the standby floor.
PARAMETER: STANDBY TRAVEL 1 FLOOR
One quiescent level can select at rope lifts. The standard value is regulating the next level.
That is the fact that if while driving the +24V DC entrance for the control and light disconnection becomes
active. The cab continues and opens the doors and switches after a certain time the light off at the next
stop. The door position is selectable. If the cab is not in full speed, then it remais in the stop and imple-
ments the functions described a while ago. Naturally also a certain quiescent level can be indicated.
Hydraulic lifts always lower into the lowest level.
Parameter: Standby Travel 1 - Offset
You have the possibility to move up (+) or down (-) the car with xxx mm in the floor. The speed is the
V0.
PARAMETER: STANDBY TRAVEL 2 FLOOR
Like the function before, you choose a second floor.
Parameter: Standby Travel 2 - Offset
You have the possibility to move up (+) or down (-) the car with xxx mm in the floor. The speed is the
V0.
PARAMETER: DOOR
Here you can choose, if the doors are open or closed in the standby travel floor.
1.) Door 1-2 open
2.) Door 1+2 open/close
3.) Door 1 open
4.) Door 2 open
5.) Door 1 open/close
6.) Door 2 open/close
7.) Door 1+2 always close
Parameter: Standby Travel – Floor Indicator
Here you have the possibilty to switch ON or OFF the floor indicator.
Parameter: Standby Travel – Car Indicator
Here you have the possibilty to switch ON or OFF the car indicator.
B606 – PARKING TRAVEL
General
The mechanism of park levels at a lift serves to position or the cab / cabs to locally or temporally it can
be better reacted changed flow of traffic and so the mechanical handling capacity increase. A position
of cabs can be made on two ways:
1) Temporal definition of park levels
During the mechanism of a general park level is met the following paramenter attitudes.
- Parameter: Park Trip -> Yes
- Parameter: Floor -> 1 up to max. number of stops
- Parameter: Park after -> Adjustable from 1 to 15 minutes, up to the
departure
-
Parameter: Door position -> Open/Close
2) Definition of the park levels by input signals
In the menu B72 of inputs can be specified on the free-provale entrances park stop functions for cer-
tainlevels. On an input with this function tension is applied, then this even is started as park stop, as
long
as the input is active.