KW Aufzugstechnik GmbH OPERATING MANUAL DAVID-613
DAVID-D613-V125-E 13.04.2021 Page - 162 -
B626 WLAN
The D613 allows the connection of an access point for WLAN use.
Parameter ON / OFF
The access point can be activated in this parameter.
Parameter Access Point Password
The code word for the access point is entered here. There are 10 digits for a code word.
Parameter Access Point SSID
The SSID is defined in this menu item.
Parameter Access Point Channel
Setting the AP channel between 01 and 14. Factory setting is channel 01.
Attention! The WLAN access point code is assigned once in the test field and must
be changed on site, so that no unauthorized third party has the opportunity to change
the parameterization of the lift system!
B627 SABBAT CONTROL
The D613 allows switching to Sabbat operation. There are two input functions, "Sabbat Control" and
"Sabbat Clock", for activating the Sabbat control. Both input functions are controlled externally.
When the "Sabbat Control" input is activated, the existing calls are still processed. However, no new
calls are accepted. The cabin moves into the main access area and remains open with open doors when
there are no calls.
After setting the "Sabbat Clock", the sabbath journey is started. The output function for the Sabbat op-
eration is activated when both input functions are set.
Parameter ON / OFF
In this parameter the usage Sabbat control can be activated.
Parameter Time of travel Main Floor
The continuation time for the main plane can be entered separately from the other levels. The default
value is 60 seconds.
Parameter Time of travel Floors
The continuation time for the floors can be entered separately from the main entrance level. The default
value is 30 seconds.
Parameter Stops Floors UP 1 to 16
In this parameter, the stops can be defined, namely for the upward travel in the region of the stops 1 to
16.
Parameter Stops Floors UP 17 to 32
In this parameter, the stops can be defined, namely for the upward travel in the region of the stops 17
to 32.
Parameter Stops Floors DOWN 1 to 16
In this parameter, the stops can be defined, namely for the downward travel in the region of the stops 1
to 16.
Parameter Stops Floors DOWN 17 to 32
In this parameter, the stops can be defined, namely for the downward travel in the region of the stops
17 to 32.