Unit RP 2040 RP 3035 RP 2045 Pump level
Cooling water con-
nection sockets
Inches
Thread G3/8"
external & G1/4"
internal
Thread G3/8"
external & G1/4"
internal
Thread G3/8"
external & G1/4"
internal
---
Flow of cooling water
with temperature of
15 °C
l/min
1 bar ð 2.1 1 bar ð 2.1 1 bar ð 1.3
---
Unit RP 240 E RP 245 E RP 250 E Pump level
Cooling capacity
at 20 °C W 600 800 1500 8
at 10 °C W 600 800 1440 8
at 0 °C W 600 800 1200 8
at -10 °C W 410 530 840 8
at -20 °C W 240 340 540 4
at -30 °C W 120 150 290 4
at -35 °C W 70 90 --- 4
at -40 °C W 20* 40 110 4
at -45 °C W --- 10* 40 4
at -50 °C W --- --- 20 2
Cooling water con-
nection sockets
Inches
Thread G3/8"
external & G1/4"
internal
Thread G3/8"
external & G1/4"
internal
Thread G3/8"
external & G1/4"
internal
---
Flow of cooling water
with temperature of
15 °C
l/min
1 bar ð 2.1 1 bar ð 2.1 1 bar ð 2.1
---
* measured with pump level 2
Table 40: Dual-stage refrigerating machine
Unit RP 1090 RP 2090 RP 10100 RP 290 E Pump level
Cooling capacity
at 20 °C W 800 800 400 800 8
at 10 °C W 750 710 400 770 8
at 0 °C W 720 680 400 740 8
at -10 °C W 690 650 400 720 8
at -20 °C W 660 620 400 700 4
at -30 °C W 630 610 390 680 4
at -40 °C W 600 580 370 640 4
at -50 °C W 540 520 350 540 4